| SYSTEM
OVERVIEW |
|
System
overview:
|
650VA
line-interactive UPS, large LCD volt meter
and UPS function indicators, plus UPS and
surge-only outlets
|
|
Voltage
compatibility:
|
120
|
|
Frequency
compatibility:
|
60
|
| OUTPUT |
|
Output
volt amp capacity (VA):
|
650
|
|
Output
watt capacity (watts):
|
350
|
|
Output
nominal voltage:
|
120VAC
|
|
Output
voltage regulation:
|
BATTERY
MODE: PWM sine wave 115V +/-5%
|
|
Output
frequency regulation:
|
LINE
MODE: Passes line frequency of 60Hz +/-10%
BATTERY MODE: Inverter output regulated to
60Hz +/-0.5Hz
|
|
Outlet
quantity / type:
|
8
NEMA 5-15R
|
| INPUT |
|
Maximum
input amps:
|
12A
|
|
Input
connection type:
|
NEMA
5-15P (right-angle plug)
|
|
Input
cord length:
|
6
ft./1.8 m
|
|
Recommended
electrical service:
|
120V
15A
|
| BATTERY |
|
Full
load runtime:
|
3
min. (650VA/350W)
|
|
Half
load runtime:
|
12
min. (325VA /175W)
|
|
DC
system voltage:
|
12VDC
|
|
Typical
battery lifespan:
|
4-6
years (depending on usage)
|
|
Battery
recharge rate:
|
2-8
hours to 90%
|
| VOLTAGE
REGULATION |
|
Voltage
regulation description:
|
Line-interactive
voltage regulation corrects brownouts as low
as 89V back to usable values
|
|
Brownout
correction:
|
Input
voltages between 89V and 104V are boosted
by 14%
|
| LEDS
ALARMS & SWITCHES |
|
Front
panel LEDs:
|
Front
panel LCD screen with blue backlight offers
continuous input line voltage data, plus UPS
status information on line power status, battery
power status, battery charge level and voltage
regulation operation
|
|
Alarms:
|
Audible
alarm with 15-second delay sounds to indicate
loss of utility power. Alarm can be silenced
by pressing front panel alarm cancel button.
Once silenced, alarm will re-sound when approximately
2 minutes runtime remain.
|
|
Switches:
|
Includes
2 front panel switches, one main on/off power
switch and one dual-function alarm cancel/self
test button
|
| SURGE
/ NOISE SUPPRESSION |
|
AC
surge suppression:
|
480
joules
|
|
AC
suppression response time:
|
Instantaneous
|
|
Dataline
suppression:
|
-
|
|
EMI
/ RFI AC noise suppression:
|
Yes
|
| PHYSICAL |
|
Shipping
weight (lbs):
|
15.6
|
|
Shipping
weight (kg):
|
7.1
|
|
Unit
weight (lbs):
|
14.6
|
|
Unit
weight (kg):
|
6.6
|
|
Unit
Dimensions (HWD/in):
|
Tower
format: 12 x 3.5 x 6.5 / Rackmount Shelf format:
3.5 x 12 x 6.5
|
|
Unit
Dimensions (HWD/cm):
|
Tower
format: 30.5 x 8.9 x 16.5 / Rackmount Shelf
format 8.9 x 30.5 x 16.5
|
|
Shipping
Dimensions (HWD/in):
|
6.5
x 15.5 x 11
|
|
Shipping
Dimensions (HWD/cm):
|
16.5
x 39.4 x 27.9
|
|
Material
of construction:
|
ABS
|
|
Form
factors supported:
|
Rack/Tower
|
|
Cooling
method:
|
Convection
|
| ENVIRONMENTAL |
|
Operating
Temperature:
|
+32
to +104 degrees Fahrenheit / 0 to +40 degrees
Celsius
|
|
Storage
Temperature:
|
+5
to +122 degrees Fahrenheit / -15 to +50 degrees
Celsius
|
|
Relative
Humidity:
|
0
to 95%, non-condensing
|
| COMMUNICATIONS |
|
Network
monitoring port:
|
USB
|
|
Software
and cabling included:
|
PowerAlert
Software available for free download at www.tripplite.com.
USB cable is user supplied.
|
|
WatchDog
compatibility:
|
Yes,
compatible with Tripp Lite's Watchdog system
service to restore operation to locked equipment
through soft reboot of application/OS or hard
power off/on reboot of connected equipment;
ideal for unattended kiosk applications
|
| LINE
/ BATTERY TRANSFER |
|
Transfer
time from line power to battery mode:
|
2-4
milliseconds
|
|
Low
voltage transfer to battery power:
|
Switches
to battery power as line voltage decreases
to 89V or lower switches back to AC mode as
line voltage increases to 94V or higher
|
|
High
voltage transfer to battery power:
|
Switches
to battery mode as line voltage increases
to 139V or higher, switches back to AC mode
as line voltage decreases to 135V or lower
|
| CERTIFICATIONS |
|
Certifications:
|
Tested
to UL1778 (USA), CSA C22.2 No. 107.3 (Canada),
NOM (Mexico), Class B (emissions)
|
| WARRANTY |
|
Optional
coverage:
|
3
Year : WEXT3-OMNI, 5 Year: WEXT5-OMNI
|
|
Product
warranty:
|
2-year
product warranty
|
|
Connected
equipment insurance (USA and Canada Only):
|
$200,000
connected equipment insurance (USA & Canada
only)
|
| SPECIAL
FEATURES |
|
Cold
Start:
|
Yes,
inverter can be cold started to enable temporary
AC output during a power failure
|
|
Appearance:
|
Attractive
black color scheme
|