| SYSTEM
OVERVIEW |
|
System
overview:
|
Line
interactive 2U rack / tower UPS protects equipment
from blackouts, brownouts, overvoltages, surges
and line noise. Maintains AC output during
blackouts and continuously corrects brownouts
and overvoltages from 75 to 147 volts. Supports
enhanced monitoring of UPS and line power
conditions via built-in USB and DB9 serial
ports, included PowerAlert monitoring software
and complete cabling. Includes slot for SNMPWEBCARD
accessory. Built-in set of 3 load management
banks offer remote reboot of selected loads
or load shedding to enhance battery runtime
for critical loads. Expandable with BP36V15-2U
battery pack (limit 1).
|
|
Voltage
compatibility:
|
120V
AC
|
|
Frequency
compatibility:
|
60
Hz
|
| OUTPUT |
|
Output
volt amp capacity (VA):
|
1500
|
|
Output
watt capacity (watts):
|
1000
|
|
Output
nominal voltage:
|
120V
AC
|
|
Output
voltage regulation:
|
LINE
MODE: Sine wave line voltage 120V (-18% /
+8%), BATTERY MODE: Sine wave output 120V
+/-5%
|
|
Output
frequency regulation:
|
LINE
MODE: Passes line frequency of 60Hz +/-10%
BATTERY MODE: Inverter output regulated to
60Hz +/-0.5Hz
|
|
Outlet
quantity / type:
|
8
NEMA 5-15R
|
|
Customized
load management receptacles:
|
Includes
3 load banks, each with 2 outlets, that support
load shedding and remote reboot on demand
of locked network devices. Controllable via
PowerAlert software to automatically switch
off optional loads, like monitors, to increase
available runtime for servers and other critical
devices.
|
|
Overload
protection:
|
15A
input breaker
|
| INPUT |
|
Maximum
input amps:
|
10.1A
/ 1090 watts
|
|
Input
connection type:
|
NEMA
5-15P
|
|
Input
cord length:
|
10
ft., 14 gauge
|
|
Recommended
electrical service:
|
15A
120V
|
| BATTERY |
|
Full
load runtime:
|
10
minutes (1000 watts), add 1 BP36V15-2U for
37 minutes
|
|
Half
load runtime:
|
25
minutes (500 watts), add 1 BP36V15-2U for
79 minutes
|
|
Expandable
battery runtime:
|
Supports
extended runtime with optional BP36V15-2U
external battery pack (limit 1)
|
|
DC
system voltage:
|
36
VDC
|
|
Typical
battery lifespan:
|
3-6
years, depending on usage
|
|
Battery
recharge rate:
|
2-4
hours to 90%
|
|
Replacement
Battery Cartridge:
|
RBC93-2U
|
| VOLTAGE
REGULATION |
|
Voltage
regulation description:
|
Automatic
Voltage Regulation (AVR) circuits maintain
clean, regulated computer-grade 120V nominal
output, without using battery power, during
brownouts to 75V and overvoltages to 147V
|
|
Overvoltage
correction:
|
Input
voltages between 128 and 147VAC are reduced
by 12%
|
|
Brownout
correction:
|
Input
voltages between 95 and 104VAC are boosted
by 12%
|
|
Severe
brownout correction:
|
Input
voltages between 75 and 94VAC are boosted
by 24%
|
| LEDS
ALARMS & SWITCHES |
|
Front
panel LEDs:
|
5
front panel LEDs - Green POWER LED, Green
VOLTAGE CORRECTION LED, 3 color BATTERY CHARGE
LED, 3 color OUTPUT LOAD LEVEL LED, red BATTERY
WARNING LED.
|
|
Alarms:
|
3
function audible alarm indicates power failure
conditions (4 short beeps every 10 seconds),
overload (continuous short beeps) and low
battery (continuous tone)
|
|
Switches:
|
Yes,
includes 2 front panel mounted push-button
switches for system enable, self-test and
alarm cancel functions
|
| SURGE
/ NOISE SUPPRESSION |
|
AC
surge suppression:
|
480
joules
|
|
AC
suppression response time:
|
Instantaneous
|
|
EMI
/ RFI AC noise suppression:
|
Yes
|
| PHYSICAL |
|
Shipping
weight (lbs):
|
53
|
|
Shipping
weight (kg):
|
23
|
|
Unit
weight (lbs):
|
43.5
|
|
Unit
weight (kg):
|
19.7
|
|
Unit
Dimensions (HWD/in):
|
3.5
x 17.5 x 13.5
|
|
Unit
Dimensions (HWD/cm):
|
8.89 x 44.5 x 34.3
|
|
Shipping
Dimensions (HWD/in):
|
9
x 24 x 20.25
|
|
Shipping
Dimensions (HWD/cm):
|
22.9
x 61 x 51.4
|
|
Material
of construction:
|
Steel
|
|
Form
factors supported:
|
Rack/Tower
(2U)
|
|
Cooling
method:
|
Built-in
cooling fan
|
|
Battery
Access:
|
Battery
access door allows hot swap battery replacement
without powering connected equipment off
|
| ENVIRONMENTAL |
|
Operating
Temperature:
|
+32 to +104 degrees Fahrenheit / 0 to +40
degrees Celsius
|
|
Storage
Temperature:
|
+5 to +122 degrees Fahrenheit / -15 to +50
degrees Celsius
|
|
Relative
Humidity:
|
0
to 95%, non-condensing
|
|
Line
mode BTU/hr. (Max.):
|
81.9
|
|
Battery
mode BTU/hr. (Max.):
|
277.9
|
| COMMUNICATIONS |
|
Network
monitoring port:
|
Includes
2 built-in monitoring ports, 1-USB & 1-DB9.
Each supports on battery, low battery, power
restored, AC line voltage, DC battery voltage,
load percentage, battery charge current, battery
capacity, internal UPS temperature and line
frequency status messaging. Interface supports
timed inverter shutoff after unattended shutdown,
activate self-test and 10 second reboot of
connected equipment. Supports reboot of all
connected devices at once via software interface.
Compatible with Tripp Lite's PowerAlert software.
|
|
Software
and cabling included:
|
Includes
PowerAlert UPS monitoring software for network
and standalone operating systems. Ships with
complete USB and DB9 cabling.
|
|
SNMP
compatibility:
|
Built-in
accessory slot accommodates internal SNMPWEBCARD
and other network accessories
|
|
WatchDog
compatibility:
|
Yes,
compatible with Tripp Lite's Watchdog system
service to restore operation to locked equipment
through soft reboot of application / OS or
hard power off/on reboot of connected equipment
- ideal for unattended kiosk applications
|
| LINE
/ BATTERY TRANSFER |
|
Transfer
time from line power to battery mode:
|
2-4
milliseconds
|
|
Low
voltage transfer to battery power:
|
75V
(resets to line power as voltage increases
to 79V)
|
|
High
voltage transfer to battery power:
|
147V
(resets to line power as voltage decreases
to 144V)
|
| CERTIFICATIONS |
|
Certifications:
|
UL1778
(USA), cUL (Canada), Class B (Emissions),
NOM (Mexico)
|
| WARRANTY |
|
Optional
coverage:
|
2
year product warranty
|
|
Product
warranty:
|
$250,000
connected equipment insurance (USA / Canada
only)
|
|
Connected
equipment insurance (USA and Canada Only):
|
3
year, 5 year, next day and on-site warranty
coverage available for select opportunities
|
| SPECIAL
FEATURES |
|
EPO
port:
|
Includes
RJ11 EPO (emergency power off) port and cable
|
|
TVSS
grounding:
|
Includes
back panel grounding point with thumbscrew
for data line surge suppressors and other
network accessories requiring a safe grounding
point
|
|
Cold
Start:
|
Yes,
inverter can be "cold started" to enable temporary
AC output during a power failure
|
|
Appearance:
|
Attractive
black housing
|
| BATTERY
PACK ACCESSORY (optional) |
|
Battery
Pack Accessory (optional):
|
BP36V15-2U
(limit 1)
|