| SYSTEM
OVERVIEW |
|
System
overview:
|
2200VA
Line-interactive UPS system with controllable
load banks and user selectable input voltages
|
|
Voltage
compatibility:
|
120V
factory default (110V, 100V user selectable)
|
|
Frequency
compatibility:
|
50
/ 60 Hz
|
| OUTPUT |
|
Output
volt amp capacity (VA):
|
2200
|
|
Output
watt capacity (watts):
|
1600
|
|
Output
nominal voltage:
|
120V
(110V, 100V) VAC
|
|
Output
voltage regulation:
|
LINE
MODE: Sine wave line voltage 120V (-18% /
+8%)
|
|
Output
frequency regulation:
|
LINE
MODE: Passes line frequency of 60Hz +/-10%
|
|
Outlet
quantity / type:
|
4
NEMA 5-15R and 4 NEMA 5-15/20R
|
|
Customized
load management receptacles:
|
3
single outlet load banks
|
| INPUT |
|
Maximum
input amps:
|
13.3
(120V)/ 14.6 (110V)/ 16.0 (100V)
|
|
Input
connection type:
|
NEMA
5-20P (optional, user-installable NEMA 5-15P
included in box)
|
|
Input
cord length:
|
10
ft./ 3m
|
|
Recommended
electrical service:
|
20A
120V
|
| BATTERY |
|
Full
load runtime:
|
6
|
|
Half
load runtime:
|
16
|
|
DC
system voltage:
|
48V
|
|
Typical
battery lifespan:
|
4-6
years typical
|
|
Replacement
Battery Cartridge:
|
RBC94-2U
|
| VOLTAGE
REGULATION |
|
Voltage
regulation description:
|
Automatic
Voltage Regulation (AVR) circuits maintain
clean, regulated computer-grade output, without
using battery power, during brownouts to 83V
and overvoltages to 145V
|
|
Overvoltage
correction:
|
120V:
Input voltages between 127 and 145 volts AC
are reduced by 12% / 110V: Input voltages
between 116 and 133 are reduced by 12% / 100V:
Input voltages between 106 and 121 are reduced
by 12%
|
|
Brownout
correction:
|
120V:
Input voltages between 96-108 are boosted
by 12% / 110V: Input voltages between 87 and
99 are boosted by 12% / 100V: Input voltages
between 83 and 90 are boosted by 12%
|
|
Severe
brownout correction:
|
120V
only: Input voltages between 83 and 95 are
boosted by 24%
|
| LEDS
ALARMS & SWITCHES |
|
Front
panel LEDs:
|
5
front panel LEDs - Green POWER LED, Green
VOLTAGE CORRECTION LED, 3 color BATTERY CHARGE
LED, 3 color OUTPUT LOAD LEVEL LED, red BATTERY
WARNING LED.
|
|
Alarms:
|
3
function audible alarm indicates power failure
conditions (4 short beeps every 10 seconds),
overload (continuous short beeps) and low
battery (continuous tone)
|
|
Switches:
|
Yes,
includes 2 front panel mounted push-button
switches for system enable, self-test and
alarm cancel functions. Back panel includes
voltage selection dip switches for 120 / 110
/ 100 volts nominal
|
| SURGE
/ NOISE SUPPRESSION |
|
AC
surge suppression:
|
570
|
|
AC
suppression response time:
|
Instantaneous
|
|
EMI
/ RFI AC noise suppression:
|
Yes
|
| PHYSICAL |
|
Shipping
weight (lbs):
|
72
|
|
Shipping
weight (kg):
|
32.4
|
|
Unit
weight (lbs):
|
64
|
|
Unit
weight (kg):
|
28.8
|
|
Unit
Dimensions (HWD/in):
|
3.5
x 17.5 x 19
|
|
Unit
Dimensions (HWD/cm):
|
8.9
x 44.5 x 48.26
|
|
Shipping
Dimensions (HWD/in):
|
9
x 23.5 x 20
|
|
Shipping
Dimensions (HWD/cm):
|
23
x 59.7 x 50.8
|
|
Material
of construction:
|
Steel
|
|
Form
factors supported:
|
Rackmount
or tower ( w/ 2-9USTAND)
|
|
Cooling
method:
|
Fan
|
|
Battery
Access:
|
Battery
access panel allows hot swap replacement without
powering connected equipment off.
|
| ENVIRONMENTAL |
|
Operating
Temperature:
|
+32
to +104 degrees Fahrenheit
|
|
Storage
Temperature:
|
+5
to +122 degrees Fahrenheit
|
|
Relative
Humidity:
|
0
to 95%, non-condensing
|
| COMMUNICATIONS |
|
Network
monitoring port:
|
HID-compliant
USB port and RS232
|
|
Software
and cabling included:
|
Includes
PowerAlert UPS monitoring software for all
common network and standalone operating systems.
Ships with 2 cables, 1-USB to USB & 1-DB9
to DB9
|
|
SNMP
compatibility:
|
Built-in
accessory slot accommodates internal SNMPWEBCARD
and other network accessories
|
|
WatchDog
compatibility:
|
Yes,
compatible with Tripp Lite's WatchDog system
service software to restore operation to locked
equipment through soft reboot of application
/ OS or hard power off/on reboot of connected
equipment - ideal for unattended kiosk applications
|
| LINE
/ BATTERY TRANSFER |
|
Transfer
time from line power to battery mode:
|
2-4
milliseconds
|
|
Low
voltage transfer to battery power:
|
Switches
to battery power if line voltage decreases
to 83 (120V), 87 (110V), or 83 (100V) volts
or less. Resets back to line power as line
voltage increases to 87 (120V), 92 (110V),
or 87 (100V) volts or higher.
|
|
High
voltage transfer to battery power:
|
Switches
to battery power as line voltage increases
to 145 (120V), 133 (110V), or 121 (100V) volts
or higher. Resets back to line power when
line voltage decreases to 141 (120V), 129
(110V), or 118 (100V) volts or less.
|
| CERTIFICATIONS |
|
Certifications:
|
Tested
to UL1778 (USA), CSA C22.2 No. 107.3 (Canada),
RoHS compliant, Class A (Emissions), NOM (Mexico)
|
| WARRANTY |
|
Optional
coverage:
|
3
year, 5 year, next day and on-site warranty
coverage available for select opportunities
|
|
Product
warranty:
|
2 year product warranty
|
|
Connected
equipment insurance (USA and Canada Only):
|
$250,000
connected equipment insurance (USA / Canada
only)
|
| SPECIAL
FEATURES |
|
EPO
port:
|
Includes
RJ11 EPO (emergency power off) port and interconnection
cable
|
|
TVSS
grounding:
|
Includes
back panel grounding point with thumbscrew
for data line surge suppressors and other
network accessories requiring a safe grounding
point
|
|
Cold
Start:
|
Yes,
inverter can be "cold started" to enable temporary
AC output during a power failure
|
|
Appearance:
|
Attractive
all-black housing
|
| BATTERY
PACK ACCESSORY (optional) |
|
Battery
Pack Accessory (optional):
|
BP48V242U
(limit 1) and BP48V60RT3U (multi-pack compatible)
|